Description
PLEASE CONTACT US FOR A QUOTE – [email protected] OR 678-383-6420
![]() |
||||||||||||||
| MODEL | A | B | D | E | F | G | H | L | M | Z | FILTERS | *INSIDE CABINET |
WEIGHT (lbs) without motors | |
| SIZE | QUANTITY | |||||||||||||
| SIS-9DD | 24 3/8″ | 19 3/8″ | 10 1/4″ | 11 13/16″ | 6 9/32″ | 7 1/16″ | 7 1/16″ | 19 1/4″ | 16 9/16″ | 21 1/4″ | 16″ x 24″ x 1″ | 1 | 24″x 24″ | 70 |
| SIS-10DD | 28 3/8″ | 21 3/8″ | 11 3/8″ | 13 1/8″ | 7 5/8″ | 8 1/2″ | 8 1/2″ | 20 1/2″ | 18 9/16″ | 25 3/4″ | 15″ x 20″ x 1″ | 2 | 28″x 28″ | 87 |
| SIS-12DD | 32 3/8″ | 24 5/8″ | 13 7/16″ | 15 5/8″ | 8 3/8″ | 9 15/32″ | 9 15/32″ | 25 3/8″ | 21 9/16″ | 30 3/4″ | 20″ x 25″ x 1″ & 16″ x 25″ x 1″ |
1 & 1 | 32″x 32″ | 117 |
| *CURB SIZE TO BE SMALLER THAN INSIDE CABINET TO ALLOW FOR FLASHING AND ROOFING. | ||||||||||||||
| **INCLUDES FILTER SECTION. | ||||||||||||||
| MODEL | MOTOR | AIRFLOW (CFM @ Static Pressure) | |||||||||||||||||
| HP | Variable Speed | Max RPM | 0″ | 1/2″ | 1″ | 1 1/4″ | |||||||||||||
| High | FEI | Low | FEI | High | FEI | Low | FEI | High | FEI | Low | FEI | High | FEI | Low | FEI | ||||
| SIS9DD050EC | 1/2 | Y* | 1200 | 1600 | – | 750 | – | 1450 | – | 600 | – | 1200 | – | 500 | – | 450 | – | 400 | – |
| SIS9DD100EC | 1 | Y* | 1200 | 2050 | 0.59 | 750 | 1.85 | 1950 | 0.75 | 600 | 1.5 | 1200 | 1.11 | 500 | 1.17 | 450 | 1.07 | 400 | 1.06 |
| SIS10DD050EC | 1/2 | Y* | 1100 | 1975 | – | 1100 | – | 1400 | – | 400 | – | 800 | – | 400 | – | – | – | – | – |
| SIS10DD100EC | 1 | Y* | 1100 | 2500 | 0.61 | 1100 | 1.57 | 2050 | 0.85 | 400 | 1.62 | 1400 | 1.11 | 400 | 1.28 | 750 | 1.23 | 300 | 1.09 |
| SIS12DD050EC | 1/2 | Y* | 1000 | 2600 | – | 1800 | – | 1925 | – | 400 | – | 850 | – | 400 | – | 600 | – | 300 | – |
| SIS12DD100EC | 1 | Y* | 1000 | 3300 | 0.58 | 1800 | 1.25 | 2800 | 0.8 | 400 | 1.37 | 2300 | 0.96 | 400 | 1.07 | 1650 | 1.07 | 300 | 0.92 |
| *Minimum motor speed 425 RPM (EC Models). | |||||||||||||||||||
| EC Motors can be controlled using the built in potentiometer on motor or by using a 0 to 10 V controller, or by a remote potentiometer. | |||||||||||||||||||
| REVIEW FAN CURVES BEFORE ADJUSTING RPM TO ENSURE LOAD DOES NOT EXCEED MOTOR HP. | |||||||||||||||||||